Skip to main content

Universal capillary thermostat, 20…150…°C, hysteresis 9.1K, TR, external setting

RTKSA-000.300

Universal capillary thermostat, 20…150…°C, hysteresis 9.1K, TR, external setting

This series of devices has been specially developed for use in heating technology in boiler systems or storage tanks, district heating transfer stations and heat transfer systems, in ventilation technology as supply air monitors or as limiters of electric heating registers as well as for controlling and monitoring temperatures on pipes and tanks. Immersion sleeves, protective coils, and fixing sets are not included in the scope of delivery. The JZ-29 fixing set must be used in conjunction with immersion sleeves or protection coils. When used as a pipe-mounted controller, the JZ-31 fixing set must be used.
  • Art.-Nr.: KA000002

    Technical data

    Ambient temperature, upper value 80 °C
    Bearing temperature, lower value -30 °C
    Bearing temperature, upper value 80 °C
    Capillary length 2 m
    Colour Anthr. grey (RAL7016), frontp. transp.
    Contact interlocking No
    Control range, lower value 20 °C
    Control range, upper value 150 °C
    Cooling control function Yes
    Depth 66,7 mm
    Device version Surface-mounted unit
    Diameter sensor element 6 mm
    Electric connection Push-in terminal
    Electronic control No
    External reset No
    External setting Yes
    Function type (systems engineering) TR
    Heating control function Yes
    Height 146,8 mm
    Internal setting No
    Length of sensor 56 mm
    Max. sensor temperature 177 °C
    Maximum air humidity (non-condensing) 95 % r.H
    Maximum switching current O: 16 (2,5) A; S: 6,3 (2,5) A, 0,25 ADC
    Maximum switching voltage 230 V AC 50 / 60 Hz, 230 V DC
    Minimum switching current At 24 V (AC/DC) min. 100 mA
    Minimum switching voltage 24 V AC / 50 Hz, 24 V DC
    Mounting / attachment In imm. sleeve, prot. coil, on tube, etc
    Number of control ranges 1
    Number of outputs 2
    Operating voltage None
    Operation Rotary knob
    Output signal Switching
    Potential free switching contact Yes
    Protection class I
    Safety and EMC In accordance with DIN EN 60730
    Scale Degree Celsius
    Sensor element Capillary tube
    Sensor material Cu
    Switching contact Two-way contact
    Switching difference 9.1 K
    Switching difference, can be adjusted No
    Switching element Microswitch
    Type of protection IP40
    Width 53 mm
    With explosion protection No
    Circuit diagram  Circuit diagram

    Downloads

    Info sheet

    Assembly instructions

    Datasheet

    Photo Type Articlenumber Features Kind
     

    Contact request

     

    Do you have questions or are you interested in our products?

    Please contact the electrician you trust or write us a message.