Universal capillary double thermostat, TR 0…120…°C, STB 70…130…°C, hysteresis TR=3K STB=-10…-15K

RTKSA-010.200

Universal capillary double thermostat, TR 0…120…°C, STB 70…130…°C, hysteresis TR=3K STB=-10…-15K

This series of devices was specially developed for use in heating technology in boiler systems or storage tanks, district heating transfer stations and heat transfer systems, in ventilation technology as supply air monitors or as limiters for electric heating registers. Immersion sleeves/protection coils are not included in the scope of delivery. The JZ-30 accessory must be used in conjunction with immersion sleeves or protection coils.
The control range / hysteresis is 0… 120 ° C / 3K for the temperature controller and 70… 130 ° C / -10… -15K for the safety temperature limiter.
  • Art.-Nr.: KA001000

    Technical data

    Ambient temperature, upper value 80 °C
    Bearing temperature, lower value -30 °C
    Bearing temperature, upper value 80 °C
    Capillary length 2 m
    Colour Anthr. grey (RAL7016), frontp. transp.
    Contact interlocking Yes
    Control range, lower value 0 °C
    Control range, upper value 120 °C
    Cooling control function Yes
    Depth 66,7 mm
    Device version Surface-mounted unit
    Diameter sensor element 6 mm
    Electric connection Push-in terminal
    Electronic control No
    External reset Yes
    External setting Yes
    Function type (systems engineering) TR/STB
    Heating control function Yes
    Height 146,8 mm
    Internal setting Yes
    Length of sensor Mm
    Max. sensor temperature 138 °C
    Maximum air humidity (non-condensing) 95 % r.H
    Maximum switching current O: 16 (2,5) A; S: 6,3 (2,5) A, 0,25 ADC
    Maximum switching voltage 230 V AC 50 / 60 Hz, 230 V DC
    Minimum switching current At 24 V (AC/DC) min. 100 mA
    Minimum switching voltage 24 V AC / 50 Hz, 24 V DC
    Mounting / attachment In imm. sleeve, prot. coil, on tube, etc
    Number of control ranges 2
    Number of outputs 4
    Operating voltage None
    Operation Rotary knob, reset button
    Output signal Switching
    Potential free switching contact Yes
    Protection class I
    Safety and EMC In accordance with DIN EN 60730
    Scale Degree Celsius
    Sensor element Capillary tube
    Sensor material Cu
    Switching contact 2 two-way contacts
    Switching difference TR: 3 K ; STB: -10 K … -15 K
    Switching difference, can be adjusted No
    Switching element Microswitch
    Type of protection IP40
    Width 106 mm
    With explosion protection No