Skip to main content

Room thermostat with timer, heating/cooling, flush-mounted, 230V AC, cover 55x55mm, pure white, gloss

KTRRUu217.456#55/V2

Room thermostat with timer, heating/cooling, flush-mounted, 230V AC, cover 55x55mm, pure white, gloss

Flush-mounted controller for time-dependent heating/cooling control of 2- and 4-pipe systems in hotel, residential and business premises. Can be adapted to almost all flat switch programs thanks to various variants. Up to 5 valve actuators (currentless open or closed) can be controlled per output. in 2-pipe operation, the operating mode can be switched over via an external contact (change-over), temperature sensor or menu. The clock can be used as a master for other controllers for ECO switching. The energy saving function (ECO) or frost protection (STANDBY) can be activated by an external contact. Alternatively, the inputs of the controller can be configured for an external temperature sensor (weighting between internal and external sensor can be set) or a dew point sensor (TPS). A fan (EC fan) can be speed-controlled via a 0 … 10 V interface.
  • Art.-Nr.: UA220005

    Technical data

    Actual temperature display Yes
    Adaptive heating time start Yes
    Ambient temperature, lower value 0 °C
    Ambient temperature, upper value 40 °C
    Bearing temperature, lower value -20 °C
    Bearing temperature, upper value 70 °C
    Clock type Day/week
    Clock version Digital
    Colour Pure white
    Control behaviour 2-point or PI-PWM
    Control range, lower value 5 °C
    Control range, upper value 40 °C
    Cooling control function Yes
    Degree of contamination 2
    Depth 46 mm
    Design Berlin UP
    Display Yes
    Display type Illuminated, graphic display
    ECO function (reduction) Yes
    ECO input (reduction) 230 V AC, 50 Hz
    ECO output (reduction) 230 V AC, 50 Hz
    Electric connection Screwed plug-in terminals
    Energy efficiency class I or IV
    External setting Yes
    Heating control function Yes
    Height 71 mm
    Housing material Plastic ABS, PC, PMMA
    Maximum air humidity (non-condensing) 95 % r.H
    Maximum power consumption Approx. 1 W (2.2 VA)
    Maximum switching current 3 (0,5) A
    Maximum switching voltage 230 V AC, 50 Hz
    Medium Air, not aggressive
    Minimum switching voltage 230 V AC / 50 Hz
    Mounting / attachment Flush mounting (deep socket recommended)
    Neutral zone Adjustable
    Number of control ranges 1
    Number of outputs 3
    Number of outputs, cooling 1
    Number of outputs, heating 1
    Number of switching programs 7
    Operating voltage 230 V AC / 50 Hz
    Operation Touch-sensitive buttons
    Output signal Switching (230 V AC, 50 Hz), 0-10 V
    Party function Yes
    Potential free switching contact No
    Power reserve Approx. 3 days
    Protection class II, following appropriate mounting
    RAL colour number (similar) 9010
    Rated impulse voltage 4000 V
    Safety and EMC In accordance with DIN EN 60730
    Sensor element NTC internal, optional NTC external
    Sensor external No
    Shortest switching time 15 min
    Surface properties Gloss
    Switching contact 2 normally open contacts
    Switching difference Room control < 1K, underfl. control < 2K
    Switching difference, can be adjusted No
    Switching element 2 relays
    Switching power 690 W
    Temperature controller version Climate controller
    Type of protection IP30
    Width 71 mm
    With explosion protection No
    Circuit diagram  Circuit diagram

    Downloads

    Assembly instructions

    Datasheet

    Photo Type Articlenumber Features Kind
     

    Contact request

     

    Do you have questions or are you interested in our products?

    Please contact the electrician you trust or write us a message.

    Close Menu