For securing hot water heating coils against freezing. The unit is intrinsically safe and has a sealable setpoint adjustment.
For measuring the temperature of non-aggressive gases. When fixing the capillary tube, mounting brackets JZ-05 / 6 M (metal) or JZ-05 / 6 K (plastic) should be used upstream of the heating coil. The capillary tube is active along its entire length. The device reacts when approx. 30 cm of the capillary tube reaches the adjusted scale value. Mounting brackets, immersion sleeves and protective coils are not included in the delivery and must be ordered separately.
  • Art.-Nr.: E6090308

    Technical data

    Ambient temperature, lower value -10 °C
    Ambient temperature, upper value 55 °C
    Bearing temperature, lower value -10 °C
    Bearing temperature, upper value 55 °C
    Capillary length 6 m
    Colour Grey
    Contact interlocking Yes
    Control range, lower value -10 °C
    Control range, upper value 12 °C
    Cooling control function Yes
    Degree of contamination 2
    Depth 55 mm
    Device version Surface-mounted unit
    Electric connection Screw terminals
    Electronic control No
    External reset Yes
    External setting Yes
    Function type (systems engineering) TB
    Heating control function Yes
    Height 105 mm
    Housing material Lower part metal, upper part plastic
    Internal setting No
    Max. sensor temperature 200 °C
    Maximum air humidity (non-condensing) 95 % r.H
    Maximum switching current 15 (8) A
    Maximum switching voltage 230 V AC, 50 Hz
    Medium Air, not aggressive
    Minimum switching current 150 mA
    Minimum switching voltage 24 V AC / 50 Hz
    Mounting / attachment Wall mounting
    Number of control ranges 1
    Number of outputs 2
    Operating voltage None
    Operation Empty
    Output signal Switching
    Potential free switching contact Yes
    Protection class I
    Rated impulse voltage 4000 V
    Safety and EMC In accordance with DIN EN 60730
    Scale Degree Celsius
    Sensor element Capillary tube
    Sensor material Cu
    Surface properties Matt
    Switching contact Two-way contact
    Switching difference Manual reset after +4K
    Switching difference, can be adjusted No
    Switching element Microswitch
    Switching power 3450 W
    Type of protection IP40
    Width 112 mm
    With explosion protection No