RTKSA-203.300
Frost protection thermostat, 12m, IP40, hysteresis +3K, STB, internal setting, external resetting
The RTKSA frost protection controllers were specially developed for air or water-side frost protection of hot water heater registers and heat exchangers in ventilation, heating or air conditioning systems. The capillaries are active along their entire length. The device responds when the minimum response length of the capillary (40 cm) reaches the set scale value. In the event of a sensor break, contact 1 – 2 is permanently open and contact 1 – 4 is permanently closed. Unlocking is no longer possible. Note: Mounting brackets, immersion sleeves and protective coils are not included in the scope of delivery and must be ordered separately. Air-side application: For the frost protection of heating registers, the capillary is clamped in front of the heating register to be protected with mounting clamps. For this, the mounting clamps JZ-05 / 6 M (metal) or JZ-05 / 6 K (plastic) are to be used.
Art.-Nr.: KA020305
Technical data
Photo | Type | Articlenumber | Features | Kind |
---|
Contact request
Do you have questions or are you interested in our products?
Please contact the electrician you trust or write us a message.