Control room double thermostat, 2x 0…50…°C, 2x TW, 2x internal setting

The plant room thermostats RTKSA were specially developed for use in industrial halls, exhibition halls, air domes and greenhouses. When used as frost protection controllers, the higher tolerances at the end of the scale must be observed. 2 separate setting ranges, heating and / or cooling.
  • Art.-Nr.: KA011101

    Technical data

    Ambient temperature, upper value 50 °C
    Bearing temperature, lower value -30 °C
    Bearing temperature, upper value 80 °C
    Colour Anthr. grey (RAL7016), frontp. transp.
    Contact interlocking No
    Control range, lower value -10 °C
    Control range, upper value 40 °C
    Cooling control function Yes
    Depth 57,5 mm
    Device version Surface-mounted unit
    Electric connection Push-in terminal
    Electronic control No
    External setting No
    Function type (systems engineering) TW
    Heating control function Yes
    Height 146,8 mm
    Internal setting Yes
    Max. sensor temperature 50 °C
    Maximum air humidity (non-condensing) 95 % r.H
    Maximum switching current O: 16 (2,5) A; S: 6,3 (2,5) A, 0,25 ADC
    Maximum switching voltage 230 V AC 50 / 60 Hz, 230 V DC
    Medium Air, not aggressive
    Minimum switching current At 24 V (AC/DC) min. 100 mA
    Minimum switching voltage 24 V AC / 50 Hz, 24 V DC
    Mounting / attachment Wall mounting
    Number of control ranges 2
    Number of outputs 4
    Operating voltage None
    Operation Internal setpoint adjuster
    Output signal Switching
    Potential free switching contact Yes
    Protection class I
    Safety and EMC In accordance with DIN EN 60730
    Scale Degree Celsius
    Sensor element Capillary tube
    Sensor material V2A
    Switching contact 2 two-way contacts
    Switching difference 1.3 K
    Switching difference, can be adjusted No
    Switching element Microswitch
    Type of protection IP54
    Width 170 mm
    With explosion protection No
    Circuit diagram  Circuit diagram