BACnet room controller flush-mounted, 230V AC, cover 50x50mm, traffic/studio white, gloss

KTRBUu217.456#27

BACnet room controller flush-mounted, 230V AC, cover 50x50mm, traffic/studio white, gloss

The alre BACnet intelligent unitary controller with graphic display was specially developed for time-dependent heating and cooling operation in 2- or 4-pipe systems. The controller can be used and applied in a wide range of areas, such as hotels, residential, office and business premises as well as hospitals and schools. The unit has two inputs and three outputs. Two of the outputs switch relays, each of which can address up to 5 actuators. The third output is analogue (0-10 V) and can be used, for example, for EC fan control. One of the two inputs is used for BACnet communication, the other can be configured for the connection of sensors, e.g. for temperature or dew point. Windows or presence contacts can be connected via BACnet. Suitable for all common switch ranges. The alre BACnet individual room controller is mounted in the flush-mounted box. The housing fits exactly into the design frames of the sizes 50 x 50 mm, 55 x 55 mm, and 60 x 60 mm from the panel switch ranges of well-known manufacturers such as Berker, Busch-Jaeger, Gira, Jung, Merten, Peha, Hager or Feller (CH). Special colors for projects on request. Communication is via BACnet in accordance with DIN EN ISO 16484-5 with the BACnet MS / TP network protocol. This makes the room controller compatible with all common building automation systems. The controller complies with the BACnet profile "B-AAC" (BACnet Advanced Application Controller) and is thus much more than a simple setpoint generator. Unlike other fieldbus interfaces such as LON or KNX, the BACnet interface does not require an additional gateway for implementation and communication with the management level. This saves costs because no service technicians with different qualifications are needed to commission the system. Another cost saving compared to distributed solutions is achieved by combining the room control unit and the intelligent unitary controller in one device. The predefined applications cover a wide range of applications for room temperature control in room automation. The BACnet room controller has been awarded the BTL certificate for compliance with the BACnet standard ISO 16484-5, which was proven by means of a BTL conformity test.
  • play pause
  • Art.-Nr.: UA230004

    Technical data

    Ambient temperature, lower value 0 °C
    Ambient temperature, upper value 40 °C
    Assembly Basic device with cover
    Bearing temperature, lower value -20 °C
    Bearing temperature, upper value 70 °C
    Colour Traffic / studio white
    Connection cross-section 0,75-2,5mm² (main), 0,08–1,5mm²
    Control range, lower value 5 °C
    Control range, upper value 40 °C
    Cooling control function Yes
    Degree of contamination 2
    Design Berlin UP
    Display type Illuminated, graphic display
    Electric connection Screwed plug-in terminals
    Heating control function Yes
    Housing material Plastic ABS, PC, PMMA
    Manual setpoint adjustment Yes
    Material quality Thermoplast
    Maximum air humidity (non-condensing) 95 % r.H
    Maximum switching current 3 (0,5) A
    Maximum switching voltage 230 V AC, 50 Hz
    Medium Air, not aggressive
    Minimum switching voltage 230 V AC / 50 Hz
    Mounting / attachment Flush mounting (deep socket recommended)
    Number of control ranges 2
    Number of outputs 3
    Operating voltage 230 V AC / 50 Hz
    Operation Touch-sensitive buttons
    Other bus systems BACnet
    Output signal Switching (230 V AC, 50 Hz), 0-10 V
    Parallel operation possible Yes
    Potential free switching contact No
    Protection class II, following appropriate mounting
    RAL colour number (similar) 9016
    Safety and EMC In accordance with DIN EN 60730
    Sensor element NTC internal, optional NTC external
    Surface properties Gloss
    Surface protection Untreated
    Switching contact 2 normally open contacts
    Switching difference < 1 K
    Switching element 2 relays
    Switching power 690 W
    Type of protection IP30
    With bus connection Yes
    With display Yes
    With LED display No
    With on-site operation Yes
    With protection against theft/dismantling No
    Circuit diagram  Circuit diagram