Skip to main content

Frost protection thermostat, 1.8m, IP40, hysteresis +3K, STB, internal setting, external resetting

RTKSA-203.000

Frost protection thermostat, 1.8m, IP40, hysteresis +3K, STB, internal setting, external resetting

The RTKSA frost protection controllers were specially developed for air or water-side frost protection of hot water heater registers and heat exchangers in ventilation, heating or air conditioning systems. If the sensor breaks, contact 1 – 2 is permanently opened and contact 1 – 4 is permanently closed. Unlocking is no longer possible. Note: Mounting brackets, immersion sleeves and protective coils are not included in the scope of delivery and must be ordered separately. The SWK-2-xxx protective coils can be used to measure the temperature of non-aggressive gases in the duct. Water-side application: For temperature measurement in non-aggressive fluids, the immersion sleeves THK-2-xxx and in aggressive fluids the immersion sleeves NTHK-2-xxx can be used.
  • Art.-Nr.: KA020300

    Technical data

    Ambient temperature, upper value 80 °C
    Bearing temperature, lower value -30 °C
    Bearing temperature, upper value 80 °C
    Capillary length 1,8 m
    Colour Anthr. grey (RAL7016), frontp. transp.
    Contact interlocking Yes
    Control range, lower value -10 °C
    Control range, upper value 15 °C
    Cooling control function Yes
    Depth 57,5 mm
    Device version Surface-mounted unit
    Diameter sensor element 9,5 mm
    Electric connection Push-in terminal
    Electronic control No
    External reset Yes
    External setting No
    Function type (systems engineering) STB
    Heating control function Yes
    Height 146,8 mm
    Internal setting Yes
    Length of sensor 98 mm
    Max. sensor temperature 120 °C
    Maximum air humidity (non-condensing) 95 % r.H
    Maximum switching current O: 16 (2,5) A; S: 2 (0,4) A, 0,25 ADC
    Maximum switching voltage 230 V AC 50 / 60 Hz, 230 V DC
    Minimum switching current At 24 V (AC/DC) min. 100 mA
    Minimum switching voltage 24 V AC / 50 Hz, 24 V DC
    Mounting / attachment Wall mounting
    Number of control ranges 1
    Number of outputs 2
    Operating voltage None
    Operation Internal setpoint adjuster, reset button
    Output signal Switching
    Potential free switching contact Yes
    Protection class I
    Safety and EMC In accordance with DIN EN 60730
    Scale Degree Celsius
    Sensor element Capillary tube
    Sensor material Cu
    Switching contact Two-way contact
    Switching difference Manual reset after +3K
    Switching difference, can be adjusted No
    Switching element Microswitch
    Type of protection IP40
    Width 53 mm
    With explosion protection No